Command
| Command | Description |
|---|---|
ATBRANCH |
Connect devices to the active circuit as a branch off a device already on it |
Prerequisites
- A FireCAD project must be open
- An active circuit must be selected in the Circuits palette
- The active drawing must be part of the project
Overview
A branch is a spur, such as a T-tap, off a device that is already on a circuit. It is not a separate circuit. The branch devices join the same circuit: they continue its addressing, their load counts toward it, and the riser draws them as a spur off the device you branched from.
Steps
- Select the circuit in the Circuits palette
- Click Branch in the Circuits palette, or type
ATBRANCH - At "Select a device on circuit '[Circuit Name]' to branch from:", pick the device the branch starts at. It must already be on the circuit
- At "Select devices to connect to '[Circuit Name]':", select the devices that make up the branch. These are devices that are not yet connected
- Press Enter
- The devices are connected as a branch. Their labels carry the branch number, for example
P2•A1.1•68for branch 1 of circuit A1
How Branch Numbers Are Given
- Devices branched in one operation share a branch number
- A new branch takes the lowest free number on that circuit. If branches 1 and 3 exist, the next branch is 2, so removing a branch does not leave a permanent gap
- To keep a number fixed, pin it in the Project Circuits palette: right-click a branch device and choose Pin Branch Number. See Reordering Devices and Setting Branch Numbers
Example
A notification appliance circuit (NAC) with two T-taps:
Panel → NAC Circuit A1
└── Strobe 1
└── Branch A1.1: Strobe 2, Strobe 3
└── Strobe 4
└── Branch A1.2: Strobe 5, Strobe 6
Tips
- The device you branch from is not changed
- Branch devices continue the circuit's address sequence; the branch number appears in the label
- Use
ATRELOCATE_BRANCHto move devices from one branch to another - Use
ATREMOVE_BRANCHto put branch devices back on the trunk of the circuit
Related Commands
- Relocating a Branch
- Removing a Branch (Preview)
- Reordering Devices and Setting Branch Numbers (Preview)
- Connecting Devices
FireCAD is the industry-leading AutoCAD add-in for fire alarm system design — from circuit layout to wire routing to code-compliant reports.
Learn more and get started at getfirecad.com →
Inspect Point Integration — Fire alarm system device lists and bill of materials can be pushed directly from FireCAD into Inspect Point, eliminating manual data entry and ensuring every device is ready for inspection scheduling and ongoing asset management.
Learn more here →