How to Show Class A Return Wiring (Preview)

Preview: this page describes the next FireCAD release, planned for December 1, and the beta available now. For the current release, see How to Show Class A Return Wiring.

Overview

When a circuit is wired as Class A, the wiring returns from the last device on the circuit back to the panel, forming a closed loop. FireCAD represents this with a Class A Return device from the Generic device palette. Connecting it as the last device on a circuit is what makes the circuit Class A in FireCAD.

New in this release: FireCAD now checks a Class A circuit's voltage drop from both ends. A Class A circuit has to keep working with an open anywhere on it, so any device may end up fed from the return end. Each device is graded on the worse of the two feeds.

Prerequisites

  • A FireCAD project must be open
  • The project must use the Generic project template, which includes the Class A Return device

Step 1: Place the Class A Return Device

Open the Device Palette and search for return to find the Class A Return device.

Class A Return device in the palette

Place it next to the panel the circuits return to. Most projects use one Class A Return device per panel.

Class A Return placed next to the FACP

Step 2: Connect the Return Device to a Circuit

Select a circuit from the panel and click Connect. The Class A Return device highlights; connect it as the last device on the circuit.

Connecting the Class A Return as the last device

The connected device list shows the length of the return wire, and wirefill is shown on any wire path segments drawn back to the Class A Return device.

Wirefill on the return path

Voltage Drop on Class A Circuits

With the Class A Return connected as the last device, FireCAD works out the voltage at each device two ways:

  • Forward feed: from the panel, along the circuit, as on any circuit
  • Reverse feed: from the return end, back along the return run and the circuit toward the panel, carrying the load from the panel side

Each device's Voltage At Device is the lower of the two. The point-to-point reports, the Design Precheck voltage drop check and the riser labels all use that value, so a long return run can no longer hide a low-voltage device.

To show both values on the point-to-point report, add the optional columns Forward Feed Voltage and Reverse Feed Voltage (Class A) in the report's column settings. The reverse value is blank on circuits that are not Class A.

Devices on a branch off a Class A circuit keep their forward value.

Notes

  • For projects with several panels, place a separate Class A Return device next to each panel
  • There is no separate setting to switch a circuit between Class B and Class A. Connecting the Class A Return device as the last device is the mechanism
  • Class B circuits are calculated exactly as before