Riser Options Reference (Preview)

Preview: this page describes the next FireCAD release, planned for December 1, and the beta available now.

Command

Command Description
ATRISER Open the Riser Options window and create a riser diagram
ATRISER_SELECTION Open the same window, then draw a riser of only the devices you select

Ribbon: FireCAD Tools > Riser > Create Riser Diagram

Overview

This page explains every setting in the Riser Options window: what it changes on the drawing, its default, when to change it, and which settings depend on each other. If you only want a good riser quickly, read Recommended Setup and When the Riser Is Too Big for a Sheet first.

The window has two panes:

  • Select Circuits (left): which circuits are on the riser, and each circuit's own settings (Wrap, Qty, Draw Left, Priority, Typical).
  • Riser Settings (right): the settings for the whole riser, in three groups: Layout Settings, Columns & Levels, and Layout Spacing, Scale & Features.

The settings are saved with the project when you click Create Riser, so the next riser (and anyone else who opens the project) starts from them. Hover over any option to see its tooltip; the drop-down options also show a small picture of each choice.

For a tour of the window with screenshots, see Riser Diagram V2.


Recommended Setup

For most projects:

  1. Device Layout Style: A (devices and panels shown once).
  2. T-Tap Spurs: Below The Run ("spur down"): each floor's run stays one straight line and the devices off a T-tap hang below it.
  3. Leave Apply Device Elevation & Column Assignments and Automatically Assign Columns on (the defaults), so floors and columns are used.
  4. Click Set Default Priorities, so the main loops are laid out first.
  5. Click Suggest Settings... (Riser IQ) once to check for anything else the project needs, then Create Riser.

If riser A does not read well for your project, try B next (each circuit draws its own copy of a device it shares with another circuit). See Device Layout Style: A to E.

When the Riser Is Too Big for a Sheet

Work down this list and stop at the first step that gives you a readable riser. Each step keeps the text at full size longer than the next.

  1. Break it up. One riser per sheet is easier to read than one riser shrunk to fit. Split it by:
    • Circuit type: in Select Circuits, use Unselect All, then Include Initiating (SLC and IDC), Include NAC & Aux or Include Audio, and create one riser for each.
    • Panel: tick only the circuits of one panel (the Grouped By Panel view makes this easy).
    • Floor or area: use Riser from Selection (ATRISER_SELECTION) and select one floor or wing on the floor plan.
  2. Fold long runs into rows. Either tick Wrap with a Qty on the long circuits, or turn on Fit To Viewport to have FireCAD cut every run to one viewport width for you (it takes over from Wrap). See Wrap and Fit To Viewport.
  3. Spread it over several sheets. Turn on Match Lines so the riser is cut into viewport-sized pieces with MATCH LINE labels, and place one viewport per piece (the Design Assistant can place the sheets for you).
  4. Make it smaller last. Lower Label Height and Device Block Scale in Riser Options and create the riser again, or ask the Design Assistant to place it at a smaller scale.

Do not use the AutoCAD SCALE command on a drawn riser. The riser's wires use labelled linetypes, and SCALE does not scale the linetype pattern, so the labels stay full size and short wires lose them. Change the size in Riser Options (Label Height, Device Block Scale) and create the riser again, or let the Design Assistant place it at the scale you want.


Device Layout Style: A to E

Device Layout Style is the kind of riser drawn. Default A.

Style What it draws When to use it
A - Devices and panels shown once Every device and every panel appears once. A device on two circuits (a speaker strobe on an audio circuit and a NAC) is drawn once, with both circuits wired to it. Use by default. It is the true picture of the system, it is what Riser IQ and the Design Assistant are built around, and it is what the riser check compares against the floor plans.
B - Devices duplicated per circuit, panels shown once Panels appear once, but each circuit draws its own copy of every device on it, so shared devices appear once per circuit. The backup. Use it when riser A is tangled because many devices are on more than one circuit; each circuit then reads as its own clean line.
C - All circuits and panels duplicated Each circuit is drawn on its own, with its own copy of its panel and devices. A circuit-by-circuit diagram, for example a point-to-point style sheet per circuit or a small system. Columns & Levels and Combine Multiple Circuits are not available with C.
D - Devices follow floorplan wirepath layout Devices are placed the way the wirepaths run on the floor plans. When the reviewer wants the riser to look like the floor plan routing.
E - Devices are summarized by elevation with quantities shown Each floor shows each device type once with a quantity, instead of every device. A compact overview of a large building (counts per floor). Voltage at device and entity properties are not shown on E.

Riser IQ only measures A, B and C risers, and never changes the layout style for you: the styles are different kinds of riser, not fixes for each other.


Riser Settings: Layout Settings

Setting Default What it does When to change it
Device Layout Style A The kind of riser (see above). Try B when shared devices tangle riser A; C, D or E for the purposes in the table above.
Device Label Position Distributed Where the device labels sit: Top Left, Top Center, Top Right, Bottom Left, Bottom Center, Bottom Right, or Distributed (split into four corners round the device). Distributed keeps long labels from pushing devices apart. A single position gives a tidier look on a small riser with short labels.
Select Entity Properties... None ticked (new properties visible on the floor plans are added automatically) Chooses which entity properties (for example LOCATION, ZONE, FLOOR) are printed with each riser device. Their values also appear under each origin in the circuit list, and the search box finds them. To show location or zone information on the riser.
Label Placements... Address and Voltage bottom right; Candela and Watts top right; Custom Properties top left; Entity Properties and Existing Marker (EX) bottom left Only shown with Distributed. Chooses the corner each label group goes in. Reset Defaults in that window puts the corners back. When you want, for example, addresses above the device.
Assign Wirepath Colors On Master switch for wire colors. Off, the three options under it are greyed and not used. Off for a single-color riser.
Apply Circuit Color Indexes On Each circuit's wires take the color set on the circuit (Project Circuits Editor). Off to ignore the circuit colors.
Use Segment Color Overrides On Uses the color override set on the circuit's origin in the drawing. Not shown in the circuit list preview, but drawn on the riser. Off to ignore the drawing overrides.
Auto Assign Missing Segment Colors Off A circuit with no color gets one by its type: SLC red, NAC blue, IDC cyan, audio magenta, access control green, wireless cyan-green, communication buses violet. On when many circuits have no color of their own.
Use Device Color Overrides Off Riser symbols take the color the device has on the floor plan. Not controlled by Assign Wirepath Colors. On when device colors carry meaning on the plans (for example existing vs new).
Show Branch Connections On Riser On Draws T-tap branches as branches off their tap device. Off, each circuit is drawn as one chain in device order and its branches are not shown. Leave on: T-Tap Spurs works on these branches. Off only for a simple chain diagram.
Combine Multiple Circuits On Where circuits run along the same path, they share one wire line instead of drawing parallel lines. Not available with C. Off if every circuit must be drawn as its own line.
Show Circuit Quantity On Adds the device count to the circuit labels. Off for shorter labels.
Show All Circuit Labels Off Each device shows its address on every circuit it is connected to, including circuits not picked for this riser. A, B and C only. On when you split the riser by circuit type but still want each device's full addressing.
Use Dashed Lines For Typical Circuits On Circuits marked Typical are drawn dashed. Off to draw typical circuits solid.
Generate Settings Table Off Places a table beside the riser listing the settings used. It widens the drawing extents. On to keep a record of the settings on the drawing, or when sending a riser for troubleshooting.

Riser Settings: Columns & Levels

This group is greyed for layout C.

Setting Default What it does When to change it
Apply Device Elevation & Column Assignments On Lays the riser out on a grid: one row per floor (device elevation) and columns (device riser column). Most options in this group need it. Leave on for any building with more than one floor. Riser IQ suggests it when devices are on several floors and it is off.
Automatically Assign Columns On Gives devices a column when you have not set one with Set Riser Column. Needs the option above. Off only if you assign every column yourself.
Separate Column Per Riser Circuit Off Each circuit that runs between floors gets its own column, so circuits do not draw over each other. Needs both options above. On when circuits cross each other between floors, mainly with Bundle Inter-Floor Connections off. FireCAD offers to turn it on when it sees many crossings.
Draw Level Lines On Draws a line at each floor. Needs Apply Device Elevation & Column Assignments. Off for a riser without floor lines.
Names... Elevation N Names the elevations (LEVEL 3, ROOF); the level line shows the name. Needs Draw Level Lines. Elevation 0 is always listed (devices with no elevation are on it). To match the floor names on the plans.
Draw Column Lines On Draws the grid column lines. Needs Apply Device Elevation & Column Assignments; greyed while Fit To Viewport is on. Off for a cleaner look.
Draw Grid Outline On Draws the frame round the grid. Same conditions as Draw Column Lines. Off for a cleaner look.
Bundle Inter-Floor Connections Into Trunk On Wires going between floors join one vertical trunk instead of each running on its own. Needs Apply Device Elevation & Column Assignments. Off to show each circuit's own riser wire. Riser IQ suggests on for a multi-floor riser when it is off.
Show Separate Return Path For Trunk Off Draws a separate return from the circuit's last device back to the trunk. Off, the circuit returns along its existing wires. Needs Bundle. On for Class A style returns into the trunk.
Separate Trunk Per Circuit Type Off One trunk per circuit type (SLC, NAC, audio...) instead of one shared trunk. Needs Bundle. On when a single trunk mixes too many systems.
Align Main Origin Panels On Lines up the main panels in each column. Your own vertical constraints win. Off if you place panels with constraints yourself.
Auto-Align Vertical Runs On A circuit that spans floors runs up one column instead of stepping right on each floor; devices in the way move right. Wrapped circuits are left as they are. Off only to get the older stepped look.
Auto-Align Branch Taps On Stacks a circuit's tap devices in one column so branches flow across in rows. Your own constraints win. Off if it pulls taps where you do not want them.
T-Tap Spurs In Line With The Run How devices hanging off a T-tap are drawn. In Line With The Run: along the floor with the run. Below The Run: the run stays one straight line and each spur drops below its tap. Alternate Below And Above: as Below, alternating sides. Works with or without Apply Levels. Set Below The Run for most projects. Alternate when spurs below crowd the next floor.
Max devices on a spur 4 (1 to 50) A branch with this many devices or fewer is drawn as a spur; a longer branch stays in line, and the short branches off its own devices become their spurs. Available when T-Tap Spurs is Below or Alternate, or Fit To Viewport is on. Raise it when branches of 5 or 6 devices should hang below; lower it when long spurs make floors too tall.
Fit To Viewport (width) Off; 2880 Keeps the riser no wider than one viewport: runs wider than the width (model space units) are cut into rows, each device moving with its spur, and circuit columns that do not fit side by side are stacked. Needs Apply Levels. On when the riser is too wide for a sheet. Set the width to the viewport width on paper times the plot scale (default 2880 = a 30 in viewport at 1/8" = 1'-0", which plots the default text at 3/32 in).
Match Lines (down every) Off; 2112 Draws MATCH LINE lines across the riser at this spacing going down (and across every viewport width on a wide riser), keeping rows clear of them, so equal viewports each show whole rows. Lines are on layer FA-ANNO-MATC. Needs Apply Levels. On to spread a tall or wide riser over several viewports or sheets. Set the spacing to the viewport height times the plot scale (default 2112 = 22 in at 1/8" = 1'-0").
Apply User Vertical Constraints Off Uses the constraints you set with Set Vertical Constraints. On after you have set constraints by hand.

Isolate Riser Circuit Columns is no longer offered; Separate Column Per Riser Circuit and Auto-Align Vertical Runs replace it.


Riser Settings: Layout Spacing, Scale & Features

Spacing & Dimensions

All sizes are in model space units, the same units as the rest of the riser.

Setting Default What it does When to change it
Minimum Device Spacing 70 The least distance between two devices, across and between rows. Raise if devices or labels feel crowded; lower for a more compact riser.
Minimum Segment Length 5 The shortest wire piece the layout makes. Rarely.
Length Between Segments 10 The gap kept between parallel wires. Raise if parallel wires run too close to read.
Grid Spacing 10 The snap interval. Only used with Snap To Grid on. Rarely.
Label Height 9 The riser text height. 9 plots at 3/32 in at 1/8" = 1'-0". To change the riser size: lower it (with Device Block Scale) for a smaller riser, then create the riser again.
Device Block Scale 1 The scale of the device symbols. With Label Height, to resize the riser.
Segment Fillet Radius 4 Rounds the wire corners. 0 gives square corners. Taste.
Line Type Label Spacing 100 The distance between the repeated labels along a wire. A wire too short for one label is drawn without it. Lower for more labels on short wires.
Line Type Label Height 6 The height of the labels in the wire linetype. Raise if wire labels are hard to read when plotted.
Trunk Junction Box Width 30 Width of the junction boxes on the inter-floor trunk. Taste.
Panel Box Width 100 Width of the dynamic panel boxes. Raise for long panel names.
Row & Column Padding 10 Space kept inside each floor row and column of the grid. Raise to separate floors and columns more.

Features & Display

Setting Default What it does When to change it
Snap To Grid On Snaps the layout to Grid Spacing. Rarely.
Ignore Labels On Device Spacing Off Spaces devices by their symbols only, not their labels. On for a tighter riser when labels may overlap a little.
Ignore Labels On Segment Layout On Routes wires without avoiding labels. Off if wires run through labels (slower, wider riser).
Use MLeader Labels (instead of linetypes) Off Wire labels drawn as MLeaders instead of being built into the wire linetype. On if your plotting or CAD standards do not handle text in linetypes.
Show Voltage At Device Off Prints the calculated voltage at each field device, red when below the circuit minimum. Not on E. On for a voltage check on the riser.
Draw Class A Return Paths On A circuit ending in a Class A Return device is drawn with its return as its own wire back to its panel, module or power supply output; the Class A Return device itself is not drawn. Off to draw the Class A Return as the last device.
Draw Dynamic Panel Boxes On Panels and other origins are drawn as boxes listing their circuits. Off to draw the panel block instead. Riser IQ warns when a device wired like a field device (for example a duct detector with a remote test station) would be boxed as a panel.
Wrapping Direction Serpentine How rows of a wrapped or fitted run follow each other: Serpentine (zigzag, each row back the other way) or Left to Right (every row the same way). Left to Right if the zigzag is hard to follow.

Select Circuits: Choosing Circuits

Control What it does
View Grouped By Part No (default), Grouped By Panel, or Compact (Flat List).
Search circuits... Filters by panel name, part number, circuit name, circuit type, and origin entity-property values.
Select All Circuits / Unselect All / Invert Tick or untick circuits in bulk.
Expand All / Collapse All Open or close the groups.
Include Initiating Ticks SLC and IDC circuits (adds to what is ticked).
Include NAC & Aux Ticks NAC and Aux circuits.
Include Audio Ticks audio circuits.
Include Other... Ticks circuits whose type contains the text you type.
Set Default Priorities Numbers every circuit: SLC and IDC 1, NAC and Aux 2, audio 3. Circuits that share devices are numbered longest first instead, so the long run stays one line.
Suggest Settings... Riser IQ (see below).
Bulk Edit Highlighted Circuits... Highlight circuits with Ctrl or Shift click, then set Include, Wrap Circuit, Draw Left, Show Typical Wiring, Priority and Wrap Device Qty on all of them at once. Each check box has three states: checked sets it on, unchecked sets it off, the middle state leaves it as it is. Click Apply to Selected.

Each circuit row shows a color swatch (the color it will be drawn in), the circuit name, its device count and its circuit types.

Select Circuits: Each Circuit's Own Settings

Setting Default What it does When to use it
Generate (the tick box by the name) Ticked for circuits you included Puts the circuit on the riser. Untick circuits to split the riser by type, panel or system.
Wrap Off Folds this circuit's long runs into rows. Greyed while Fit To Viewport is on. For the few circuits whose runs are much longer than the rest.
Qty 20 Devices per row when wrapped (1 to 999). With Apply Levels on, only devices on the run count; devices on a T-tap spur move with their tap. Pick a number that fits your sheet width. Riser IQ works out a quantity per circuit.
Draw Left Off Draws the circuit to the left of its panel, right to left. Circuits fed from it follow. Needs columns (Apply Levels and Automatically Assign Columns, or your own columns with the panel left of the devices). To balance a wide riser: put half of a panel's circuits on each side. With Fit To Viewport, a riser with Draw Left circuits takes two viewport widths.
Priority 0 (none) 1 is first, then 2, and so on. Higher-priority circuits are laid out and given columns first, and a device on two circuits is drawn with the circuit of better priority. Put the main loops first so they read as straight lines. Set Default Priorities does this for you.
Typical Off Draws the circuit as typical wiring: dashed (with Use Dashed Lines For Typical Circuits), circuit name only, and it does not shape the layout. For circuits that repeat a pattern, or that you want shown without implying a wiring order.

Wrap and Fit To Viewport

How a wrapped circuit is folded depends on the riser settings:

Riser settings What Wrap does
Apply Levels on, Fit To Viewport off The finished riser is cut into rows of Qty devices on the run. Spur devices move with their tap and are not counted, other circuits do not move, and a multi-floor circuit does not step right on each floor.
Fit To Viewport on (with Apply Levels) Wrap and Qty are greyed and not used. Fit To Viewport cuts every run to the viewport width itself.
Apply Levels off The circuit is folded during layout after Qty devices (spur devices count). Fit To Viewport has no effect without Apply Levels.

Rows follow the Wrapping Direction setting. A device on a wrapped row that starts its own circuit (a module's zone, a duct detector's test station) keeps that circuit with it.


Reset Settings to Default

Reset Settings to Default (bottom of the window) asks what to reset:

Option Ticked when the window opens What it resets
Riser settings Yes Every option in Riser Settings back to its default, including Label Height (9) and Device Block Scale (1). This also clears the chosen entity properties, the label placements and the elevation names.
Wrap and devices per row, on every circuit No Wrap off and Qty 20 on every circuit.
Draw Left, on every circuit No Draw Left off on every circuit.
Priority, on every circuit No Priority 0 on every circuit (Set Default Priorities numbers them again).
Typical wiring, on every circuit No Typical off on every circuit.

Which circuits are ticked for the riser is never reset. Cancel changes nothing.

Suggest Settings (Riser IQ)

Suggest Settings... checks the ticked circuits with the settings as they are in the window (saved or not), lays the riser out with each suggestion without drawing it, and shows the measured result: device overlaps, labels on labels, labels on devices, wires through labels, and the width in viewports. Suggestions that measured better are ticked; click Apply Ticked to set them in the window, then Create Riser.

Riser IQ can suggest: Apply Device Elevation & Column Assignments (devices on several floors), T-Tap Spurs (Below when many devices hang off taps, In Line when none do), Fit To Viewport (on when a run is wider than one viewport, off when all fit), a Wrap quantity per long circuit (when Fit To Viewport is off), Draw Left on half of a wide panel's circuits, circuit Priority (longest first among circuits sharing devices), Combine Multiple Circuits, Bundle Inter-Floor Connections Into Trunk, and Distributed labels when labels are much wider than the device spacing. It also lists things no setting fixes, such as devices that Draw Dynamic Panel Boxes would box as panels.


How the Settings Depend on Each Other

If... Then...
Layout is C Columns & Levels and Combine Multiple Circuits are greyed.
Layout is D or E Show All Circuit Labels is greyed; Riser IQ does not measure the riser.
Apply Device Elevation & Column Assignments is off Automatically Assign Columns, Separate Column Per Riser Circuit, Draw Level Lines, Draw Column Lines, Draw Grid Outline and Bundle are greyed; Fit To Viewport and Match Lines are kept but do nothing; Draw Left only reverses direction.
Fit To Viewport is on Each circuit's Wrap and Qty are greyed and ignored; spurs are drawn below their taps (In Line With The Run is greyed in the list, your choice is kept for later); Draw Column Lines and Draw Grid Outline are greyed; Max devices on a spur is used.
T-Tap Spurs is In Line (and Fit To Viewport off) Max devices on a spur is greyed.
Show Branch Connections On Riser is off Circuits are drawn as one chain, so there are no taps for T-Tap Spurs to work on.
Bundle Inter-Floor Connections Into Trunk is off Show Separate Return Path For Trunk and Separate Trunk Per Circuit Type are greyed.
Assign Wirepath Colors is off Apply Circuit Color Indexes, Use Segment Color Overrides and Auto Assign Missing Segment Colors are greyed.
Snap To Grid is off Grid Spacing is greyed.
Device Label Position is not Distributed Label Placements... is hidden.

Ask the Design Assistant

You can ask the Design Assistant about riser settings in plain words. It tells you which settings it used or changed, keeps a copy of your own settings before it tries anything else, and asks before changing settings when you have not said what you want. When you do say (a size, no wrap, a layout, keep my settings), it does exactly that, and if it cannot fit, it says so with the numbers.

Examples:

  • "What are my riser settings?"
  • "Put the riser on the sheets." (it suggests riser A with spurs below, and a split or wrap where the riser is too big, with the reasons)
  • "Make a separate riser for the SLC loops and one for the NACs."
  • "Use B instead."
  • "Wrap N1 at 10."
  • "Turn on Fit To Viewport and match lines."
  • "Why is the riser so wide?" (it can run the Riser IQ checks and explain them)
  • "Go back to my settings."

Related Commands


FireCAD is the industry-leading AutoCAD add-in for fire alarm system design — from circuit layout to wire routing to code-compliant reports.
Learn more and get started at getfirecad.com →

Inspect Point Integration — Fire alarm system device lists and bill of materials can be pushed directly from FireCAD into Inspect Point, eliminating manual data entry and ensuring every device is ready for inspection scheduling and ongoing asset management.
Learn more here →

Was this article helpful?
0 out of 0 found this helpful