Preview: this page describes the next FireCAD release, planned for December 1, and the beta available now. For the current release, see Adding a Circuit Pair.
New in the next release
- Circuit pairs are being retired. Use a segment label override instead: it changes only the text on the wire, so the circuit is not counted on wires it does not run on. For the return run of a circuit sharing a conduit, override the label with
[fill] + SPAREor the text you need. See Overriding Segment Labels (Preview). - The command still works, and existing circuit pairs keep counting in wire labels and wire fill as before. It now prints "Circuit pairs are being retired. Use Override Segment Label (ATOVERRIDE_SEGMENT_LABEL) and [fill] + SPARE instead."
- To turn a drawing's existing circuit pairs into label overrides, type
ATCONVERT_CIRCUIT_PAIRS. Each label keeps reading as it does now, and the pairs are removed so wire fill and reports count only the circuits actually routed on the segment. - In the Project Circuits palette, the Add Circuit Pair and Remove Circuit Pair buttons are replaced by Override Segment Label.
Command
| Command | Description |
|---|---|
ATADD_CIRCUIT_PAIR |
Add circuit pair associations to selected segments |
Prerequisites
- A FireCAD project must be open
- An active circuit must be selected in the Circuits palette
Overview
The ATADD_CIRCUIT_PAIR command adds the active circuit's wire to the wirepath segments you select, even though those segments are not on the circuit's own device-to-device path. Use it to count a second run of the same circuit in a pathway, for example the return run of a Class A circuit that shares a conduit with its outgoing run. The wire labels and wire fill then include it.
Steps
- Select the active circuit in the Circuits palette
- Type
ATADD_CIRCUIT_PAIRin the AutoCAD command line - Select the segment entities to pair
- Press Enter to confirm
- The active circuit's wire is added to the selected segments, and the wire labels update
Tips
- If nothing is selected, FireCAD shows "Nothing was selected, please try again."
- The added wire counts in the wire labels and wire fill on those segments
- To take it off again, use Removing a Circuit Pair, or convert it to a label override with
ATCONVERT_CIRCUIT_PAIRS