Relocating a Device's Circuit Connections (Preview)

Preview: this page describes the next FireCAD release, planned for December 1, and the beta available now. For the current release, see Relocating Circuit Origin.

Command

Command Description
ATRELOCATE Move a device's circuit connections to another device

Ribbon: FireCAD > Circuits > Relocate Device Circuit

Prerequisites

  • A FireCAD project must be open
  • The active drawing must be part of the project

Overview

ATRELOCATE takes the circuits a device is connected to and moves those connections to another device. Use it when a device was connected and then replaced, or when you drew a second symbol and want it to take over the first one's place on the circuit. The receiving device takes the same position in the circuit, so the wiring order and addresses carry over.

It moves a device's connections, not the circuits a panel originates. To move a whole circuit's devices onto another circuit, see Relocating an Entire Circuit (Preview).

Steps

  1. Type ATRELOCATE
  2. At "Select a device to relocate circuit(s) from:", pick the connected device
  3. At "Select device circuits to relocate", pick which connection to move. Each connection is listed by the device's address label, or choose ALL to move every connection
  4. At "Select a device to relocate circuit(s) to:", pick the device that should take over
  5. If the receiving device has more than one input of that type, choose which one
  6. Keep going with the next device, or press Escape to finish

When It Refuses

The receiving device needs a free input of the same circuit type as the connection you are moving:

Message Meaning
Device doesn't contain the required circuit type The receiving device cannot connect to that kind of circuit
Device circuit already connected Its matching input is already in use

Tips

  • Both devices must be in the same drawing
  • Entity properties carry over to the receiving device
  • Labels are refreshed when the command finishes