Panel Summary Report (Preview)

Preview: this page describes the next FireCAD release, planned for December 1, and the beta available now. For the current release, see Panel Summary Report.

New in the next release

  • One voltage drop method for the whole project: Voltage drop calculation (Panel Summary and Design Precheck), Point-To-Point or Lump Sum, set in Options > Reports and in this report's settings. The Design Precheck judges voltage drop the same way.
  • A card's used amps is now the larger of its standby and alarm current, instead of their sum. Standby and alarm are listed separately, and a boosted circuit (IDNAC, ES-MX) shows its boost on its own line.
  • Card capacity is read from the card that originates the circuits, not from the panel assembly.

Watch the Video

Open the video in a new tab (Placing the Panel Summary, 65 seconds).

Command

Command Description
ATREPORT_PANEL_SUMMARY Generate panel summary tables in the drawing

Ribbon: FireCAD > Reports > Panel Summary

Prerequisites

  • A FireCAD project must be open

Overview

Places panel summary tables in model space: for each selected panel, its components, circuit details and calculations, voltage drop, and secondary power (battery) requirements, ending with the batteries to provide. Place them inside the model-space frame of the sheet they belong on, the same way the other report tables are shown through the sheet's viewport. When the project has speaker circuits (a voice system), the battery calculation uses at least 15 minutes of alarm, even if Alarm Time in the window shows less.

Steps

  1. On the FireCAD Tools tab, open the Reports panel and choose Panel Summary (or type ATREPORT_PANEL_SUMMARY)
  2. In Report Settings, tick the panels to include on the left
  3. On the right, pick the Voltage Drop Calculation Method (Point-To-Point or Lump Sum) and check Battery Sizing (standby time, alarm time, derating factor, spare capacity)
  4. To keep the tables compact, tick Show Only Circuit Current Totals (Hide Part Details), and set Report Text Height for the sheet's scale so the text prints at a readable size
  5. Click Accept, then pick the insertion point in model space

Tips

  • Report text height is in drawing units. On a sheet at 1:48, a text height of 4.5 prints at about 3/32"
  • Several panels are placed side by side; on a busy project, generate one panel at a time so each set of tables fits its sheet

Related Commands