Preview: this page describes the next FireCAD release, planned for December 1, and the beta available now. For the current release, see Potter Data Export.
Command
| Command | Description |
|---|---|
ATEXPORT_POTTER_DATA |
Export the project's Potter panels, loops and devices to a file Potter's programming software imports |
Ribbon: FireCAD > Export > Export Potter Data
Prerequisites
- A FireCAD project must be open
- The project must contain at least one Potter panel
Overview
Export Potter Data writes the project's Potter fire alarm panels, their SLC loops and the devices on each loop to a FireCAD Data File (.fpcad), which Potter's panel programming software imports. You design and address the system in FireCAD, then hand the panel programmer a file instead of retyping every point.
Steps
- Click Export Potter Data on the Export panel, or type
ATEXPORT_POTTER_DATA - FireCAD checks the project first. If it finds anything the import may not accept, a summary lists it (see below) and asks Continue exporting anyway? Click No to fix the issues first, or Yes to export as it is
- Choose where to save the file. The default name is the project name followed by Potter Data
- Click Save
What the Check Reports
| Item | What it means |
|---|---|
| Panels with no name were given a placeholder | Name the panel with Set Device Name so the export uses your name |
| SLCs with no circuit name were given a placeholder | Name the loop's circuit |
| Devices skipped: Point Type not configured | The part has no Potter point type in the device catalog |
| Devices skipped: Function not configured | The part has no Potter function in the device catalog |
| Circuits skipped: no circuit template | The circuit was not built from a circuit template |
| Panel model not recognized | Potter imports IPA60, IPA100, IPA4000, AFC50, AFC100, AFC1000, ARC100 and PFC4064 panels |
| V-suffix model normalized | A model such as IPA4000V was exported as its base model, IPA4000 |
| Loops included under their parent panel | Loop expanders in booster cabinets, connected to the panel over P-LINK, are exported as loops of that panel |
| Loops not exported | A loop on a device that is not a Potter panel and has no P-LINK path to one |
If a part is skipped for a missing point type or function, contact FireCAD support with the part number and we will add it to the catalog.
Related Commands
FireCAD is the industry-leading AutoCAD add-in for fire alarm system design — from circuit layout to wire routing to code-compliant reports.
Learn more and get started at getfirecad.com →
Inspect Point Integration — Fire alarm system device lists and bill of materials can be pushed directly from FireCAD into Inspect Point, eliminating manual data entry and ensuring every device is ready for inspection scheduling and ongoing asset management.
Learn more here →