Preview: this page describes the next FireCAD release, planned for December 1, and the beta available now. For the current release, see Options & Configuration.
Command
| Command | Description |
|---|---|
ATOPTIONS |
Open the Options Editor |
Ribbon: FireCAD > Edit > Options
Prerequisites
- A FireCAD project must be open
Overview
The Options Editor sets how FireCAD draws labels, builds reports, works with circuits and manages drawing elements. Settings apply to the current project, except the Design Assistant key and connection settings, which are stored for your Windows user.
The editor has eight tabs.
Text and Attributes
| Setting | Description |
|---|---|
| Device Attribute Text Height | Height of device attribute text |
| Scale Device Attribute With Block | Attribute text scales with the block |
| Apply Dimscale To Device Blocks | Apply the drawing's dimension scale to device blocks |
| Wirepath Label Text Height | Height of wire path label text |
| Riser Text Height / Riser Block Scale | Text height and block scale in risers |
| Hide Wirepath Labels On Short Segments | Segments shorter than this length get no label |
| Show Segment ID In Wirepath Labels Instead Of Wirefill | Label segments with their ID; generate the Segment Label Schedule for reference |
| Mask Device Label Text / Mask Wirepath Label Text | A background mask behind label text |
| Generate Line Types For Wirefill Instead Of Labels | Draw wirefill into the wire's line type instead of as a label |
| Line Type Text Spacing | Spacing of the text in those line types |
| Default Delimiter | The character between label parts |
Changed: Show Circuit Quantity In Wirepath Labels is gone; put [QTY] in the wire path label format instead. Report Text Height moved to the Reports tab.
Tools
| Setting | Description |
|---|---|
| ATPoly Fillet Radius (Units) | Corner radius used by ATPOLY
|
| Block Replacement: Alignment Mode, Rotation Mode, Scale | How replacement blocks line up, rotate and scale. Scale 0 keeps the existing block's scale |
| Block Recognition: Recognize devices updated with Edit Block In Place | New. FireCAD keeps recognizing devices whose blocks you edited in place |
Layers
The layers FireCAD puts new elements on: Riser Layer, Report Layer, Wirepath Layer and Wirepath Label Layer. Leave a setting blank to use the active layer.
Circuits
| Setting | Description |
|---|---|
| Additional Wire Length Factor % | Added to calculated wire lengths for slack and routing |
| Add Wire Label To Circuit Devices Without Complete Wirepaths | Label devices even when their wire path is incomplete |
| Show Connection Status Icons In Model Space / Connection Status Icon Size | Connection status icons on devices |
| Show Wirepath Status Icons In Model Space / Wirepath Status Icon Size | Status icons on wire paths |
| Wirepath Intersection Tolerance | How close a line must end to a device to count as connected to it |
| Add Virtual Wirepath Between Intersecting Devices | Connect touching devices with a virtual wire path |
| Device Highlight Padding | Space around a highlighted device |
| Device Coverage Transparency | Transparency of coverage overlays |
| Copy Device Connections When Validating Copied Devices | New. What Validate does when it finds devices you copied: Always copy their connections, Never copy, or Ask each time. Choose Ask each time to bring the prompt back after choosing Don't ask again |
Reports
Rebuilt in this release. The report windows keep the same settings: a change here or in a report's own window is the same setting.
| Group | Settings |
|---|---|
| Voltage drop calculation (Panel Summary and Design Precheck) | Point to point or Lump sum. The panel summary uses it, the Design Precheck judges voltage drop the same way, and the Design Assistant works to it |
| Display precision (digits) | Length, Current, Voltage, Watts |
| Report text and layout | Report Text Height, Symbol Scale Factor, Don't Include Unused Circuits, Add Reports and Risers to Current Drawing |
| Battery calculation (NFPA 72) | Standby Time, Alarm Time, Derating Factor, Spare Capacity (extra capacity on top of derating: required Ah = load x derating x (1 + spare %)), Only Show Circuit Totals on Battery Calculation |
| For all reports | Report Width Override (Drawing Units): one width for every report, or Auto. Settings each report also keeps show as partly filled (or (varies)) when the reports differ; leave them so to keep each report's own value, or set them to apply to every report |
Removed: Report Column Width Factor, Include Existing Devices in Legend/BOM and Generate Legacy Reports.
Drawing
Drawing Units: the unit system of the current drawing.
Project
| Setting | Description |
|---|---|
| Project File Backup Quantity | How many backup copies of the project file to keep. 0 turns backups off |
| Embed Project Backup In Drawings | Embed a compressed project backup in each drawing on save, for recovery with ATRESTORE_FROM_DRAWING. See Embedded Drawing Backup & Recovery
|
Design Assistant (new)
Design preferences the assistant works to (voltage drop method, voltage margin, spare capacity, speaker voltage, mounting, ceiling height, standing instructions), your own Anthropic API key, the progress card, and the Claude Desktop connection. See Options: Design Assistant Tab (Preview).
Saving and Loading Settings
| Button | Action |
|---|---|
| Apply | Save changes and update the drawing |
| Cancel | Close without saving |
| Load Settings... | Load settings from a saved .xml file |
| Save Settings As... | Save the current settings to an .xml file to reuse in other projects |
| Reset Settings | Reset settings to their defaults |
When you click Apply, FireCAD saves the settings, updates device and wire path labels in the active drawing if label settings changed, and refreshes its cached values. A progress window shows the update; you can cancel the label update.
Tips
- Use Save Settings As before experimenting, and Load Settings to go back
- The battery settings (standby, alarm, derating, spare capacity) drive the battery calculation reports and the Design Precheck. Set them to your project's NFPA 72 requirements
- Pick the voltage drop method once on the Reports tab; the panel summary, the Design Precheck and the Design Assistant all follow it
Related Articles
FireCAD is the industry-leading AutoCAD add-in for fire alarm system design — from circuit layout to wire routing to code-compliant reports.
Learn more and get started at getfirecad.com →
Inspect Point Integration — Fire alarm system device lists and bill of materials can be pushed directly from FireCAD into Inspect Point, eliminating manual data entry and ensuring every device is ready for inspection scheduling and ongoing asset management.
Learn more here →