Preview: new in the next FireCAD release, planned for December 1, and in the beta available now.
Command
| Command | Description |
|---|---|
ATEXPORT_FIREWORKS_DWG |
Save a copy of the drawing with device labels as plain text, for import into Edwards FireWorks |
Ribbon: FireCAD Tools > Export > Export Fireworks Drawing
Prerequisites
- A FireCAD project must be open, with a project drawing active
- The drawing must be saved: the export is made from the saved file
Overview
Edwards FireWorks graphics read device addresses and names as plain text. A FireCAD device label is an attribute inside the device block, which FireWorks cannot see. Export Fireworks Drawing writes a copy of the drawing in which each device's visible labels are turned into single-line text at the same position, height, rotation, style and layer.
Your project drawing is never changed. The copy is a separate drawing: it is not part of the project, and FireCAD will not treat it as a project drawing if it is opened later.
Steps
- Save the drawing
- On the FireCAD Tools tab, in the Export panel, click Export Fireworks Drawing (or type
ATEXPORT_FIREWORKS_DWG) - Choose which devices to export as text:
- SLC and relay devices (the default): devices on an SLC, including addressable relay and control modules. Notification appliances and power supplies without an SLC connection are left as blocks
- Selected devices: only the devices you selected before running the command
- All devices: every FireCAD device in the drawing
- Choose what happens to the device symbols:
- Explode to lines and arcs (the default)
- Keep as blocks without attributes
- Choose where to save the copy. FireCAD suggests the drawing name followed by - FIREWORKS
- Choose Yes to open the exported drawing, or No
The command line reports how many devices were exported, how many labels were written as text and how many symbols were exploded, and confirms that the project drawing was not changed.
Tips
- Blocks that are not FireCAD devices, such as the title block and north arrow, are never changed
- A symbol scaled differently on X, Y and Z can't be exploded by AutoCAD. Its labels are still written as text, it is kept as a block, and the command line lists it
- Labels that span several lines are written as one text per line
- If FireCAD says the project has no devices recorded for the drawing, validate the drawing first and run the export again