DUPLICATED DEVICES IN BATTERY CALCULATIONS

The issue described here is that battery calculations show certain devices (most commonly slc modules) multiple times, some showing standby and alarm current values and others showing values of 0.

00.png

To correct this error, launch the project device editor.

01.png

Choose the tab as shown below and follow steps 1 and 2 to see the device entered in the correct template and selection group.

02.png

The cause of this error is that the CRF-300 is entered in a second selection group and it should not be there.

04.png

The error can be fixed by removing the CRF-300 module from the assigned devices list in the second address selection group template.

05.png

In this case, the CRF-300 module is compatible with two SLC circuit types, SLC MODULES/SENSORS and SLC MODULES, depending on which control panel it is connected to.

Because of this, we must repeat the process for the other SLC circuit type. 

06.png

Now when we generate a battery calculation both modules are listed showing the correct standby and alarm current values.

07.png