The issue described here is that battery calculations show certain devices (most commonly slc modules) multiple times, some showing standby and alarm current values and others showing values of 0.
To correct this error, launch the project device editor.
Choose the tab as shown below and follow steps 1 and 2 to see the device entered in the correct template and selection group.
The cause of this error is that the CRF-300 is entered in a second selection group and it should not be there.
The error can be fixed by removing the CRF-300 module from the assigned devices list in the second address selection group template.
In this case, the CRF-300 module is compatible with two SLC circuit types, SLC MODULES/SENSORS and SLC MODULES, depending on which control panel it is connected to.
Because of this, we must repeat the process for the other SLC circuit type.
Now when we generate a battery calculation both modules are listed showing the correct standby and alarm current values.